| Ue | Rated operational voltage of the assembly | 400 V or 415 V AC line-to-line; 230 V or 240 V AC line-to-neutral | Match the network nominal voltage and the voltage ratings of all devices, busbars and insulation systems | Assembly rating plate, design calculations and dielectric test records |
| InA | Rated current of the assembly | 63 A to 4,000 A in the examples above | Select at or above the calculated maximum demand current, considering diversity, continuous loads and future capacity | Load schedule, diversity calculation and temperature-rise verification |
| Inc | Rated current of an individual circuit | 16–630 A for common outgoing circuits | Coordinate with cable ampacity, protective-device setting and actual load current | Circuit schedule, cable sizing and protective-device coordination study |
| Icw | Rated short-time withstand current for a specified duration | 25, 50, 65 or 80 kA rms for 1 s are common project ratings | Icw should meet or exceed the short-circuit current that can flow until the protective device clears the fault | Short-circuit calculation and assembly short-circuit verification |
| Ipk | Rated peak withstand current | Often approximately 2.1–2.2 times the corresponding 50 Hz rms short-circuit value, subject to the system characteristics | Check electrodynamic forces on busbars, supports and connections during the first peak | Peak fault-current calculation and design-verification evidence |
| Icc | Rated conditional short-circuit current when protected by a specified device | Commonly specified for assemblies using current-limiting incoming protection | Use only with the declared protective device, settings and installation conditions | Manufacturer or designer coordination data and protective-device declaration |
| IP rating | Protection against access, solid objects and water ingress | IP31–IP42 for controlled indoor rooms; IP54–IP66 for dusty, wet or outdoor locations | Select according to dust, water, cleaning method, ventilation and access conditions | Enclosure IP declaration and installation inspection |
| Form of internal separation | Physical segregation between busbars, functional units and terminals | Form 1, Form 2, Form 3b or Form 4b | Use higher separation where maintenance safety, fault containment or continuity of service is important | Assembly drawings, segregation details and routine verification |
| Ambient temperature | Temperature surrounding the assembly during service | Indoor design basis commonly 35 °C average over 24 hours; outdoor conditions may be higher or lower | Apply derating for high ambient temperature, compact layouts and heat-producing devices | Thermal calculation, ventilation design and operating limits |
| Altitude | Installation elevation above sea level | Up to 2,000 m is a common reference condition; higher elevations require assessment | Check reduced dielectric strength, cooling performance and device derating above the reference altitude | Project environmental data and equipment derating schedule |
| Pollution degree | Expected contamination level affecting insulation | Degree 2 for clean indoor locations; Degree 3 for industrial or outdoor environments | Use appropriate creepage distances, enclosure protection and contamination controls | Insulation coordination assessment and environmental classification |
| Neutral conductor loading | Current carried by the neutral, including triplen harmonics | May approach or exceed phase current in installations with many single-phase nonlinear loads | Assess data-processing equipment, LED drivers, variable-speed drives and other harmonic-producing loads | Harmonic study, neutral sizing and temperature-rise assessment |